Impedance Monitoring
Your Grounding System Depends
on an Intact Resistor Path
An open or bypassed neutral grounding resistor changes how the system responds to a ground fault. Continuous resistor path monitoring helps identify that loss of protection so the installation can alarm or trip as required.
Would You Know If Your Protection Failed?
A Failed Resistor Path Can
Compromise Your Grounding System
In both high resistance grounded (HRG) and low resistance grounded (LRG) systems, an open circuit in the neutral grounding resistor (NGR) or its connections can leave the system ungrounded. A short circuit that bypasses the resistor can create a solidly grounded path, removing the intended limit on ground-fault current. Without resistor path monitoring, either condition can remain undetected until a ground fault occurs.
Protective functions should never be assumed to work. They should be verified.
Resistor Path Failure Modes
|
Failure mode
|
Effect on the system
|
|---|---|
|
Open resistor path |
The system can become ungrounded, increasing susceptibility to overvoltages to ground and making ground faults harder to locate. |
|
Short circuit bypassing the resistor |
The system loses the resistor’s intended current limitation, allowing substantially higher ground-fault current. |
Continuous monitoring identifies these changes so personnel and protection circuits can respond when the grounding path is compromised.
High resistance grounding is I‑Gard’s engineering focus. Explore the benefits of HRG →
Required in Canada.
Essential to Reliable Resistance Grounding.
CEC 2024, Section 10 and Table 17 establish monitoring and protective-response requirements for impedance-grounded installations. In a resistance-grounded system, the monitoring arrangement must detect failures of the resistor path and provide the alarm and de-energization response applicable to the installation.
These requirements address a fundamental concern: the grounding protection must remain effective throughout operation. An installed resistor can develop an open circuit, be bypassed by a short circuit, or lose a connection. Continuous monitoring makes those conditions detectable.
Compliance depends on the installed arrangement, including the monitoring relay, sensing components, settings, and connections to the alarm and trip circuits.
As a Canadian manufacturer, I‑Gard advocates continuous resistor path monitoring wherever resistance grounding is used. The need to verify the grounding path is universal.

SIGMA3-C
Ground-fault protection and resistor path monitoring for HRG and LRG systems.
SIGMA3-C continuously monitors the neutral-to-ground path, including the resistor and its connections, to detect conditions that compromise resistance grounding. It provides the monitoring function and protective outputs needed to support compliance with the installation requirements of CEC 2024, Section 10 and Table 17.
SIGMA3-C in Action
Reliable resistance grounding depends on detecting ground faults and verifying the resistor path. SIGMA3-C monitors both and, in suitably equipped HRG systems, also helps personnel locate the fault.
1. Ground-Fault Protection
Detects ground faults with an adjustable pickup level and a trip delay of 60–9,300 ms.
2. Resistor Path Monitoring
Continuously monitors the neutral-to-ground path, including the resistor and its connections, for abnormal resistance and open- or short-circuit conditions.
3. Pulsing for Fault Location in HRG Systems
With a pulsing NGR and contactor, SIGMA3-C controls a repeating change in ground-fault current. A technician traces the pulses with a clamp-on ammeter to locate the fault while operation continues.
SIGMA3-C provides separate trip, ground-fault, resistor path fault, and watchdog outputs. These connect to the installation’s alarm and trip circuits to implement the required protective response.
Two Complementary Modes for Continuous Monitoring
|
Mode
|
Active When
|
How
|
|---|---|---|
|
Measurement |
Current through the NGR exceeds 5% of its rated let-through current. |
Calculates resistance from current and voltage measured during operation. |
|
Injection |
Current through the NGR is below 5% of its rated let-through current. |
Uses high-frequency AC injection and a DC-based measurement to assess resistor path integrity, including open-path detection where parallel capacitance affects the AC response. |
Together, these modes monitor the resistor path during normal operation and ground-fault conditions.
System Capacitance Should Not Mask Resistor Path Condition
System capacitance can provide an additional path to ground for the high-frequency monitoring signal. This changes the conductance measured by the relay, even when the resistor path itself remains unchanged. Reliable monitoring must distinguish the influence of capacitance from changes in the resistor path.
SIGMA3-C supplements high-frequency AC monitoring with DC injection during Injection Mode. Because capacitance does not carry steady-state DC current, this provides an additional measurement for assessing the resistor path where capacitance affects the AC response. The monitoring settings are adjusted to suit the application.
Engineered to Work Together
Reliable monitoring depends on correctly matching the relay and sensing components to the NGR. System voltage, resistor characteristics, and current sensor selection determine the appropriate configuration.
I‑Gard manufactures these components and coordinates their selection for the application. Our engineering team can also review monitoring requirements where an NGR has already been specified or purchased.
Sensing and Display Components
SIGMA3-C uses an NGRXS sensing resistor and a ZSCS current sensor to monitor the neutral-to-ground path. The SIGMA3-C-TDM touchscreen brings system readings, alarms, and relay settings into view, helping personnel assess conditions and respond.
|
Component
|
Role
|
|---|---|
|
NGRXS Sensing Resistor |
Provides the neutral-to-ground voltage input and couples the monitoring signal into the resistor path. It is selected to suit the system voltage. |
|
ZSCS Current Sensor |
Measures current through the NGR, providing the current input for ground-fault detection and resistor path monitoring. |
|
SIGMA3-C-TDM Touchscreen Display |
Displays system readings, alarms, and event history, and provides access to relay settings. |
I‑Gard selects the sensing components to match the application’s voltage and current requirements.
Compliance & Standards




Resistor monitoring (Canada)
CSA C22.1, §10 & Table 17
Resistance-grounded systems
IEEE 242-2001 §8.2.4 · IEEE 142-2007 §1.4.3
Wiring & grounding
NEC (US) · Canadian Electrical Code (Canada)
Arc flash mitigation recognition
NFPA 70E (US) · CSA Z462 (Canada)
Typical Applications
FAQ
Frequently Asked Questions
Answers to our most commonly asked questions. Can’t find yours? Ask here
Working to a Project Specification?
Send I‑Gard your resistor monitoring requirements. Our engineering team can help confirm the SIGMA3-C configuration, sensing components, and display options for your equipment.